Model 2150

Home Products Contact Us

Model 10
Model 25
Model 30
Model 40
Model 60
Model 65
Model 110A
Model 1100A
Model 1150
Model 1175
Model 1180
Model 1200A
Model 1250
Model 1300
Model 1400A
Model 1420A
Model 1450
Model 1600
Model 1650
Model 2000T
Model 2150
Model 2200
Model 2300
Model 2500
Model 2800
Model 34xx

(Industrial)
Model 2150:    Four Digital Input / Four Digital Output Network Node

Datasheet   

Description

The Model 2150 is a LonWorks based product that has four isolated relay outputs and four isolated inputs.   All inputs and outputs are communicated via Standard Network Variable Types (SNVT). The outputs are four Form C relays.  Form C relays are single pole double throw with Normally Closed and Normally Open output contacts.   Four red LEDs indicate the status of the output relays. The four isolated inputs are capable of detecting a wide range of low voltage AC or DC input.  The inputs can be used with voltage output, dry contact, sinking (NPN), and sourcing (PNP) type devices.  All inputs and outputs have transient voltage suppression. Four green LEDs indicate the presence of an input signal. Additionally, the Model 2150 includes a flexible firmware layer that includes two Temperature Alarm Blocks, two Percent Alarm Blocks, four Hardware Input Blocks and four Hardware Output Blocks.  The Firmware Blocks can be used individually or tied together to accomplish more complex logic.  For example, a relay output can be tied to the Temperature Alarm Block to turn on a warning light if a temperature set point is exceeded. For efficient use of input power, the Model 2150 uses a switching power supply.  It can operate from a wide range of low voltage DC or AC.

Key Features

bulletVery compact design available in DIN Rail and NEMA 4X enclosures.
bulletLonWorks FTT-10A network interface with all inputs and outputs communicated via Standard Network Variable Types (SNVT)
bulletSwitching power supply allows operation from a wide range of low voltage AC or DC.
bulletFour isolated outputs via Form C relays with transient voltage clamps and LED status indicators.
bulletFour isolated inputs capable of handling 3-36VDC or 3-24 VAC @ 50/60 Hz.  Inputs have transient voltage protection and LED status indicators.
bulletRemovable terminal blocks on all connections.
bulletTwo non-dedicated Temperature Alarm Blocks.
bulletTwo non-dedicated Percent Alarm Blocks.
bulletInputs have user configurable debounce.
bulletOutputs are controlled via a flexible output block that is capable of user specified Boolean logic functions on multiple Input Network Variables.
bulletOutputs have configurable minimum on and off time to prevent equipment damage and tailor output waveform.
bulletOutputs types of pulse, toggle, cycle, and flash are supported.
 
Home
Up
Send mail to webmaster1@neurologic-research.com with questions or comments about this web site.
Copyright © 2005, NeuroLogic Research Corporation
Last modified: December 07, 2005